Setting the LIS-SV

This section supplements the “LIS-SV” product manual. The parameters described here are only available if the LIS-SV is used in an ABULiner control unit.

 

 

Overview of the 'ABULiner' parameter level

The following parameters can be set in the 'ABULiner' parameter level of the LIS-SV.

 

Parameter

Designation

See

5.10

Calling up the parameter level

Accessing the 'ABULiner' parameter level

5.11

Activating the LIS-SV for the ABULiner

Activating/deactivating the LIS-SV for the ABULiner

5.11

Setting the gear ratio

Setting the gear ratio

5.12

Activating double lifting speed

Activating double lifting speed on the LIS-SV

5.14

Setting the run-on time of the auxiliary fan

Setting the run-on time of the auxiliary fan

 

Warnung stürzende Last

Danger during setting work!

During setting work on the LIS-SV, monitoring of the wire rope hoist is switched off. This means the wire rope hoist cannot be monitored for excess load, among other things.  This means the wire rope hoist cannot be monitored for excess load, among other things.

This in turn means the load could fall and kill or injure people!

Do not use the crane for normal work during setting work, and only lift loads very carefully for test purposes!

 

 

Accessing the 'ABULiner' parameter level

All LIS-SV parameters which are important for the ABULiner are combined in a separate parameter level, which is shown as a submenu.

 

---Khakee- The Bihar Chapter -Season 1- WEB-DL -H...

 

 

*    Move the load hook out of the limit switch range (up or down).

During parameter setting, the load hook must not be within the limit switch range.

*    Open the menu of the LIS-SV. See the documentation “Load indicator system LIS-SV”.

 

 

---Khakee- The Bihar Chapter -Season 1- WEB-DL -H...

Enter button

Arrow buttons

*    Select parameter 5.10.

*    Press ENTER.

●   The 'ABULiner' parameter level is activated.

●   Parameter 5.11 is displayed.

 

 

Exiting the 'ABULiner' parameter level

---Khakee- The Bihar Chapter -Season 1- WEB-DL -H...

Enter button

Arrow buttons

*    Select parameter 5.99.

*    Press ENTER.

●   The previous parameter level is reactivated.

●   Parameter 5.10 is displayed.

 

 

Activating/deactivating the LIS-SV for the ABULiner

The LIS-SV is automatically activated for the ABULiner if a value is entered for the parameter 5.11.

In the ABULiner mode (a value is set for parameter 5.11):

─     The LIS-SV can monitor the total load for a maximum of two wire rope hoists.

─     Input F3 (normally used for measuring the load of wire rope hoist 3) now serves in monitoring the current rotational frequency of the hoist motor.

─     A value can be entered for parameter 3.0 (maximum load capacity of wire rope hoist 3). If a value is entered for this, parameter 5.11 cannot be set.

─     This interlocking thus excludes an incorrect setting.

─     The load-controlled switching point at output TxD of the LIS-SV cannot be used.

─     Parameter 4.5 (setting for load-controlled switching point) is not available.

 

 

In the normal mode (no value is set for parameter 5.11):

─     Operation of the ABULiner Lifting/Lowering unit is not possible.

─     The LIS-SV can monitor the total load for up to three wire rope hoists.

─     Input F3 serves in measuring the load of a third wire rope hoist.

─     A value can be entered for parameter 5.11 (gear ratio). If a value is entered for this, parameter 3.0 cannot be set.

─     This interlocking thus excludes an incorrect setting.

─     The load-controlled switching point at output TxD of the LIS-SV can be used.

─     Parameter 4.5 (setting for load-controlled switching point) can be used.

 

 

Setting the gear ratio

The LIS-SV uses the signal of the encoder and the gear ratio of the hoisting gear to calculate the hook travel distance, the maximum distance in the limit switch range and the current rotational frequency of the hoist motor. The gear ratio must be set on the machine.

 

 

---Khakee- The Bihar Chapter -Season 1- WEB-DL -H...

Cable speed

 

*    Read off the type designation at the type plate of the wire rope hoist.

*    Read off the cable speed.

 

 

*    From this table, select the gear ratio that matches the cable speed.

 

Cable speed

Hoist motor GM

32 m/min at 50 Hz
38 m/min at 60 Hz

25 m/min at 50 Hz
30 m/min at 60 Hz

20 m/min at 50 Hz
24 m/min at 60 Hz

16 m/min at 50 Hz
19 m/min at 60 Hz

800.4

50.01

63.49

77.77

98.16

800.5

47.03

60.04

74.66

95.03

1000.6

54.43

68.91

84.00

105.1

1000.7

54.60

68.06

81.45

104.6

2000.3

58.22

74.23

91.19

118.4

3000.4

73.61

93.92

118.4

152.9

5000.3

85.14

109.3

132.8

169.0

5000.4

80.20

104.9

127.7

160.6

6000.3

94.69

118.5

149.6

182.7

7000.1

118.0

148.3

182.6

232.0

Table: Gear ratios (numerical values) depending on hoist motor (lines) and cable speeds (columns) at 50 and 60 Hz.

 

 

---Khakee- The Bihar Chapter -Season 1- WEB-DL -H...

Enter button

Arrow buttons

*    Move the load hook out of the limit switch range (up or down).

During parameter setting, the load hook must not be within the limit switch range.

*    Select parameter 5.11.

*    Press ENTER.

●   The set value is displayed.

If the value is 0.00, the function is deactivated.

●   Hold ENTER pressed.

●   CODE is displayed.

*    Hold ENTER pressed.

 

 

---Khakee- The Bihar Chapter -Season 1- WEB-DL -H...

Enter button

Arrow buttons

*    Enter the code 1443.

*    Press ENTER briefly.

 

 

---Khakee- The Bihar Chapter -Season 1- WEB-DL -H...

Enter button

Arrow buttons

*    Set the value from the table.

If the display ‘0.00’ cannot be changed, a value is set in parameter 3.0.  In this case, set the value to zero first.

*    Press ENTER briefly.

 

 

---khakee- The Bihar Chapter -season 1- Web-dl -h... May 2026

“Khakee: The Bihar Chapter” is a web series that premiered on Netflix in 2022. The show is a crime drama that revolves around the life of a police officer, sub-inspector Abhishek Singh, who is transferred to the Bihar Police. The series is set in the backdrop of Bihar, a state in eastern India known for its rich cultural heritage and complex socio-political landscape.

The show is available to stream on Netflix. You can also search for “Khakee: The Bihar Chapter - Season 1 WEB-DL” online to find links to download or stream the series. However, be sure to use reputable sources to avoid any copyright or malware issues. ---Khakee- The Bihar Chapter -Season 1- WEB-DL -H...

The Indian web series landscape has witnessed a significant surge in recent years, with numerous platforms offering a wide range of content. One such series that has garnered attention from audiences and critics alike is “Khakee: The Bihar Chapter.” This article will delve into the details of the show, its plot, characters, and what makes it a must-watch. “Khakee: The Bihar Chapter” is a web series

“Khakee: The Bihar Chapter” is a must-watch for fans of crime dramas and those interested in exploring the complexities of contemporary India. With its talented cast, gripping narrative, and nuanced themes, the show is sure to keep audiences engaged. If you’re looking for a series that will keep you on the edge of your seat, look no further than “Khakee: The Bihar Chapter.” The show is available to stream on Netflix

The show has received widespread critical acclaim for its gripping narrative, strong performances, and nuanced exploration of complex themes. The series has been praised for its realistic portrayal of life in Bihar, which adds to its authenticity.

The show follows the journey of Abhishek Singh, played by Karan Tacker, as he navigates the complexities of the Bihar Police. Upon his transfer, he is tasked with solving a series of crimes that take him deep into the heart of the state’s underbelly. As he delves deeper into the cases, he uncovers a web of corruption, crime, and deceit that threatens to upend the very fabric of the state’s law and order.

Khakee: The Bihar Chapter - Season 1: A Gripping Web Series**

 

 

Only for auxiliary fans

 

Setting the run-on time of the auxiliary fan

The auxiliary fan of the hoist motor continues to run for several minutes after the lifting or lowering. This ensures that the hoist motor is adequately cooled even at slow lifting speeds. The run-on time can be adjusted.

 

---Khakee- The Bihar Chapter -Season 1- WEB-DL -H...

Enter button

Arrow buttons

*    Move the load hook out of the limit switch range (up or down).

During parameter setting, the load hook must not be within the limit switch range.

*    Select parameter 5.14.

*    Press ENTER.

●   The set value is displayed.

 

 

---Khakee- The Bihar Chapter -Season 1- WEB-DL -H...

Enter button

 

*    Set the value to between 3 and 10 minutes using the arrow buttons.

*    Press ENTER.